Features:
Advance DSP digital control technology.
Active input power factor correction(PFC)
Frequency adaptive system
Ultra wide input voltage range
Input power factor is 0.9
Ultra wide input frequency range
Strong scalability
Green and environment protection
Specifications:
Specifications:
Model | AF1K | AFKL | AF2K | AF2KL | AF3K | AF3KL | AF6K | AF6KL | AF10K | AF10KL | |
Capacity | 1KVA/900 W | 2KVA/1.8KW | 3KVA/2.7KW | 6KVA/5.4KW | 10KVA/9KW | ||||||
Battery Voltage | 12V7AH*2 | 36VDC | 12V7AH*4 | 72VDC | 12V7AH*6 | 96VDC | 12V7AH*16 | 192VDC | 12V7AH*16 | 192VDC | |
Size, D*W*H(mm | 350×144×230 | 350×144×230 | 425×190×328 | 425×190×328 | 425×190×328 | 425×190×328 | 533×260×560 | 425×190×328 | 533×260×560 | 533×260×501 | |
Net Weight(kgs) | 9 | 6 | 18.4 | 10 | 23.4 | 11 | 55 | 12.2 | 62 | 21 | |
Input | |||||||||||
Input voltage | 90V-285Vac | 120-275VAC | |||||||||
Frequency Range | 40 Hz~70 Hz | 46~54 Hz or 56~64 Hz | |||||||||
Phase | Single Phase With Ground | ||||||||||
Power Factor | >=0.99 @ 100% Load |
Output |
|||||||||||
Output Voltage | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 208/220/230/240 VAC | |||||||||
AC Voltage Regulation | ±1% | ||||||||||
Frequency Range(Synchronize Range) | 40~46 Hz or 54~60 Hz | 46~54 Hz or 56~64 Hz | |||||||||
Frequency Range(Batt. Mode) | 50 Hz ±0.25 Hz or 60 Hz ±0.3 Hz | 50 Hz or 60 Hz ±0.1 Hz | |||||||||
Current Crest Ratio | 3:1 | ||||||||||
Output current | 4.5A | 9.1A | 13.6A | 27A | 45A | ||||||
Harmonic Distortion | ≤3% THD(Linear Load) ≤6% THD(Non-linear Load ) |
≤3% THD(Linear Load ) ≤5% THD(Non-linear Load ) |
|||||||||
Overload | 105%±5%<Load≤125%±5%:After 50secs turn to bypass and alarm ;125%±5%<Load≤150%±5%:after 25secs turn to bypass and alarm; load>150%±5%:after 300ms turn to bypass and alarm. | 105%±5%<Load≤125%±5%:After 1mins turn to bypass and alarm ;125%±5%<Load≤135%±5%:after 30secs turn to bypass and alarm; load>135%±5%:after 300ms turn to bypass and alarm. | |||||||||
Transfer Time | AC Mode to Batt. Mode | Zero | |||||||||
Waveform(Batt. Mode) ) |
Pure Sinewave |
Efficiency | |||||||||||
Battery Mode | 85% | 92% | 92% | ||||||||
Battery | |||||||||||
Battery Type | 12 V/7 Ah | Depending on applications | 12 V/7 Ah | Depending on applications | 12 V/7 Ah | Depending on applications | 12 V/7 Ah | Depending on applications | 12 V/7 Ah | Depending on applications | |
Battery Numbers | 2 | 4 | 6 | 16 | 16 | ||||||
Recharge Time | 8 hours recover to 90% capacity | 9 hours recover to 90% capacity | |||||||||
Charging Current | 1 A | 6.5A | 1 A | 5.5A | 1 A | 5.5A | 1 A | 5.5A | 1 A | 5.5A | |
Environment | |||||||||||
Operation Humidity | 20-90% RH @ 0-40ºC Non-condensing | 0-95% RH @ 0-50ºC Non-condensing |
0-95% RH @ 0-40ºC Non-condensing |
||||||||
Noise Level | Less than 50dBA @ 1 Meter | Less than 55dBA @1 Meter |
Less than 58dBA @1Meter |
||||||||
Management | |||||||||||
Smart RS-232 | Support windows® 2000/2003/XP/Vista/2008, windows® 7/8, Linux, Unix and MAC | ||||||||||
Optional SNMP | Power management from SNMP management and web browser |